Lubrication Controllers

A lubrication controller is the part of the system that decides when — it times the pump cycles, watches line pressure or flow, and raises an alarm when lubrication stops reaching the points. A centralized system without a controller is a pump someone has to remember; with one, the machine greases itself on schedule and reports its own failures.

On single-line systems the controller rests the line between cycles so meter units and injectors can reset; on dual-line systems it alternates the two main lines and watches the crossover pressure that tells it both sides fed. The controller is chosen to match that pump and line logic — and its power supply to the machine.

IsoHiTech catalogs two controllers here: the automatic lubrication system controller for centralized grease pumps (12V, 24V and 110-240V supplies) and the Bijur Delimon SM-AC control timer for SMAC-type systems.

Choosing the Right Controller

Your systemRight controllerCataloged as
Grease pump, mobile machine (12V/24V)Automatic controllerLubrication system controller
Fixed installation, mains supplyAutomatic controllerLubrication system controller (110-240V)
Bijur SMAC-type systemOEM timerBijur SM-AC control timer

Cataloged Models

ModelSpecificationCatalog page
Lubrication System ControllerCycle control for centralized grease pumps, 12V/24V/110-240V, alarm outputsystem controller
Bijur SM-AC Control TimerProgrammable timer for SMAC-type lubrication systemsSM-AC timer

Lubrication Controller FAQ

What does a controller actually watch?

Three things, in order of value: time (run the pump on your schedule), pressure (confirm the line reached operating pressure — a failed line never does), and fault time (a pump that runs but never reaches pressure within its window is flagged). Time-only control greases a broken system faithfully; pressure feedback is what turns a controller into protection.

How do I set the cycle interval?

Start from the grease specification and the bearing list, not from habit. Short cycles with small doses beat long soakings — friction drops and seals are not flushed out. Set the interval so the total daily grease matches the machine’s calculated demand, then review after a month of bearing temperatures. As a worked example: a bearing list totaling 30 g/day on a pump moving 1.5 g/min needs about 20 minutes of pumping per day — one 2-minute cycle every 2.4 hours beats one 20-minute soaking once a day.

12V/24V or mains controller?

Follow the machine, not the workshop. Mobile equipment and vehicles give you 12V or 24V; fixed production machinery gives you mains. The cataloged controller takes all three supply ranges, so the same unit serves both shelves of a plant.

Can a controller replace a failed Bijur timer in place?

The SM-AC is the direct answer for SMAC-type systems — same programming model, same mounting class, and your existing interval and fault-time settings transfer to the new unit, so the machine’s lubrication plan survives the swap. For other systems, send the failed timer’s model and the pump type through the contact page and the team confirms the match before anything ships.

Does IsoHiTech help size the whole control loop?

Yes — send the pump model, point count and machine duty cycle through the contact page, and the team specifies the controller settings in writing: interval, run window and alarm threshold, so the unit starts up configured rather than at factory defaults.